Tested build blueprint · November 2026 · works with the Shelly app and Home Assistant
1. What you get, and what you don’t
This build lets you arm and disarm a DAS NetworX NX-8 alarm panel from the Shelly app or Home Assistant. It works by electrically “pressing” a keyswitch input on the panel, using one hardwired zone.
What it does:
- Remote arm and disarm from your phone (from anywhere, if you enable Shelly cloud or Home Assistant remote access).
- Needs no codes in the app: the panel treats the pulse like a keyswitch.
What it doesn’t do:
- It is toggle-only. Every pulse flips the alarm: armed to disarmed, or disarmed to armed. The panel does not tell the Shelly which state it is in, so the app cannot show “armed” or “disarmed”. Always check the keypad’s On light (or listen for the siren chirp) before pressing.
- Remote disarm is a security risk. Anyone who gets into your Shelly account, Wi-Fi or Home Assistant can disarm your alarm. Use strong, unique passwords, keep the Shelly off the open internet, and think carefully before exposing the button to voice assistants.
Safety and scope:
- All the wiring is low voltage (12 V DC). The mains stays at the wall socket: the panel is powered by a 16 V AC plug-pack and a 12 V battery, and no 230 V enters the cabinet. If you find mains wiring inside the cabinet, stop and call a licensed electrician.
- If the alarm is monitored, tell your monitoring company before you open the cabinet. Check your insurance and any warranty.
- This is a hobbyist guide, not professional advice. You do this at your own risk.
Tested on: DAS NetworX NX-8 board (marked “51-DAS-1”, Direct Alarm Supplies), firmware label 34.00 (D34E, 06/03/05), LED code pad, Optex RX-40QZ motion detectors, Shelly Plus Uni, Shelly app 3.77. It is sold in Australia as the Hills Reliance R8; a forum post says it is the same family as the Caddx NX-8, but your unit’s firmware may differ, so test every step.
2. How it works
- The NX-8 has a zone type called KEY-SWITCH (type 30). A zone sealed with a 3.3 k? resistor is “idle”; a momentary short across the zone toggles arm and disarm.
- The Shelly Plus Uni has two potential-free solid-state relay outputs (30 V, 300 mA). OUT 1 is wired in parallel with the 3.3 k? resistor, so closing the relay shorts it.
- A 3-second auto-off timer in the Shelly turns each tap into a sustained pulse (giving the panel’s processor enough time to register a disarm command even during an active alarm).
- The Shelly runs from the panel’s 12 V (POS and COM).
- The panel has only four hardwired zones, and all were in use. So the build merges two motion-detector loops into one zone (wired in series, with a single end-of-line resistor) and uses the freed zone as the keyswitch input. If you already have a spare zone, skip that part.
3. Shopping list
Core parts:
- Shelly Plus Uni (the older Gen 1 “Shelly Uni” wires differently).
- One 3.3 k? resistor, ¼ W, through-hole, 5% or 1% tolerance. Altronics R7052 (“3K3 0.25W carbon film resistor, pack of 10”) fits. Check for “3K3” or “3.3k” in the title and orange-orange-red bands. A “3.3 Ohm” part is 1,000 times too small, and surface-mount MELF parts have no legs.
- Wago 221-412 (2-way) × 2: the loop joint plus a spare.
- Wago 221-415 (5-way) × 1: to tap POS.
- About 20 cm of 0.5 mm² red hookup wire (the POS jumper) and a 3 cm offcut of wire (the detector link).
- Small heat shrink (2–3 mm) or PVC tape, cable ties, Velcro or double-sided tape, masking tape and a marker.
Tools:
- Digital multimeter (any with a 20 k? range).
- Small flat screwdriver (about 2.5 mm), Phillips screwdriver, wire strippers, side cutters.
- Heat gun, lighter or hairdryer if you use heat shrink.
- Phone for photos.
Not needed: ESP8266 or NodeMCU boards, extra relays, interface modules.
Budget: the parts other than the Shelly come to roughly A$15–25. Check current prices.
4. Know your panel
Terminal strip, left to right with the board’s labels along the bottom (see Illustration 3): Z1, COM, Z2, Z3, COM, Z4, POS, COM, DATA, AUX 2, SMOKE, COM, SIREN, AUX 1, EARTH, AC, AC.
- Always land wires by the printed label, never by counting screws. The ninth terminal is DATA, the keypad bus.
- All COM terminals are common.
- POS is the panel’s 12 V auxiliary supply.
- AUX 1 and AUX 2 are negative-switched outputs, usually driving a strobe or sounder. SIREN is a speaker driver. Don’t connect anything of yours to them in this build.
- Default zone types (Feature 18): zone 1 = type 1 (entry/exit), zone 2 = type 3 (entry/exit, chime), zones 3 to 8 = type 16 (instant).
- Each detector loop is a green and a yellow wire. Red and black are the detector’s 12 V power.
- The Optex RX-40QZ keeps a 3.3 k? resistor in series with its alarm contact and tamper switch. That is the panel’s “end of line”.
5. Before you start
- Find your installer (program) code. The factory default is 9713, or 971300 on systems that use six-digit codes. If it was changed, you need the new one. Never use the factory-default keystrokes, which wipe the panel.
- Check for single end-of-line resistors. Enter programming (
*8, code,0#), then22#and press*four times with no digits. LED 4 (zone 4) must be off. Press#. If it is on, dual end-of-line is enabled and this design needs changes: stop. - Read your zone types:
18#, then*only. Zone lights add up as 1, 2, 4, 8, 16. Choose two interior motion zones of the same type that are not entry/exit zones, ideally in nearby rooms. This guide uses zones 3 and 4, with zone 4 becoming the keyswitch. Use your own numbers if you choose differently. - Open both chosen detectors and confirm each has a 3.3 k? resistor in its terminal block.
- Photograph the terminal strip and every detector terminal block.
Programming rules:
- Pressing
*with no digits only reads data. Digits change settings. - Wait over 10 seconds after any power-up before pressing keys.
- You cannot step backwards within a feature. Press
#and re-enter it.
6. Build steps
Part A: Prepare the parts on the bench
- Meter the resistor: it should read about 3.30 on the 20k range (3.14 to 3.47 is fine).
- Tape-flag the Shelly’s two OUT 1 wires (they look like the supply negative). Plus Uni pigtail colours: red = VAC1 (12 V in), black = VAC2 (supply negative), black pair marked OUT 1 = relay 1, black pair marked OUT 2 = relay 2 (unused), orange = IN1, brown = IN2, white = analog in, yellow, blue, grey (+5 V), green (GND) and purple (counter): all unused.
- Strip about 11 mm off each OUT 1 wire. Slide short heat shrink over each, twist one resistor leg onto each wire for 5 or 6 turns, slide the sleeve over the twist and shrink it. Leave a few millimetres of bare tip to go under the terminal screw (see Illustration 2).
- Insulate each unused Shelly wire separately, especially the grey +5 V wire, and tie the unused OUT 2 wires back.
Part B: Identify which yellow is which (panel on, disarmed)
- Pull one yellow wire from the COM terminal shared by the two zones you are merging, for a moment.
- Note which zone light comes on at the keypad. That is the detector whose loop you broke.
- Put it back, confirm the light goes out, and tape-flag each yellow with its zone.
Part C: Free a zone by merging two loops
- Power down: unplug the 16 V AC plug-pack from the wall socket, then pull the battery’s red lead. Confirm the keypad is dark. The cabinet’s tamper switch may beep when you reconnect power: silence it with a user code.
- Call the lower zone A and the higher zone B (here A = Z3, B = Z4).
- Pull B’s green from its terminal. Join it to A’s yellow in a Wago 221-412. The loop becomes: A green, detector A, A yellow, Wago, B green, detector B, B yellow, COM (see Illustration 4).
- Open one detector. Remove its 3.3 k? resistor and replace it with a short wire link under the same two screws the resistor’s legs were under. Without the link, the loop is open. On the Optex RX-40QZ, the link goes from the right-hand screw of the TAMPER block to the first N.C. screw of the ALARM block (see Illustration 5).
- Keep the removed resistor out of the detector: it must not touch any terminal. The merged loop needs exactly one 3.3 k? resistor in total.
- Close both detector covers fully. The tamper switch is part of the loop.
Part D: Wire the Shelly
- Keyswitch pair. The twisted OUT 1 wire and resistor leg from Part A: one pair under the freed zone’s terminal (Z4), the other under the COM next to it (the COM between Z3 and Z4). Tug-test both (see Illustration 3).
- Shelly 12 V positive. Move the existing wires off POS into a Wago 221-415, add the Shelly’s red, and run a short red jumper from the Wago to the POS screw.
- Shelly negative. Land the Shelly’s black under any COM terminal (we used the COM between SMOKE and SIREN). Check no strands touch SMOKE (a 12 V supply) or SIREN. The green wire isn’t needed: we twisted it with the black, but you can leave it insulated.
- Tie everything tidy. Fix the Shelly inside the cabinet with Velcro, away from the circuit board.
Part E: Power up and verify the merged zone
- Reconnect the battery’s red lead, then plug in the AC plug-pack. Wait over 10 seconds before pressing keys.
- Wait 2 to 3 minutes for the PIRs to warm up. A zone light flashes during warm-up.
- Expect Ready on and zone lights off. The freed zone (Z4) may show open until Part F.
- Walk past each detector. The merged zone (Z3) should light for both. A PIR’s red LED may stay dark after warm-up if its LED jumper is off, so use the walk test:
*, Chime, master code, walk, then enter the master code again.
Part F: Programme the keyswitch zone
*8: the five function lights (On, Partial, Exit, Bypass, Chime) flash.- Enter the program code: the Service light flashes and the five lights go steady. If not, the code was rejected: try 971300.
0#: the Armed light comes on steady.18#: the Armed light goes out and the Ready light comes on.- Press
*once per zone before your zone (three presses for zone 4). The lights show the type of each zone you pass. On the tested panel: lights 1+2 (type 3), light 3 (type 4), lights 1+2+3 (type 7), and the same again. Your values may differ. - Type
30: Ready flashes and lights 2, 3, 4 and 5 are lit. Press*to store it. #, then Exit and Exit. Wait about 12 seconds.
Part G: Bare-wire test (no Shelly yet)
- Touch a bare wire across the freed zone’s terminal and its COM for about a second. The system should arm, and the siren may chirp once.
- Stay out of the PIRs’ view while armed.
- Touch again: it disarms, and the siren may chirp twice.
Part H: Shelly app setup
- In the Shelly app, add the device and join your 2.4 GHz Wi-Fi network. Metal cabinets block Wi-Fi: check the signal strength inside the closed cabinet.
- Open the device, then scroll the left icon column to Settings. Set relay type: Detached and Power on default: Off, then Save. Detached stops the unused input wires from pulsing the relay.
- In the Timer tab, tick Auto off, enter 3 seconds and Save. Without this, you have to tap twice for each action. The 3-second duration is critical to ensure the panel registers remote disarm commands even while it is actively sounding the siren.
- Rename channel 1 “Alarm” and channel 2 “Unused”. Hide or ignore channel 2.
- Set a device password (the Shelly’s web page and access point), and consider an app pin lock. Decide about cloud access: you can disable it and use Home Assistant only.
- Test: one tap arms, one tap disarms. The button will always read “Turn on”: it shows the relay, which pulses and returns to off, not the alarm’s state.
Part I: Home Assistant
- Home Assistant normally discovers the Shelly on the local network. Add it under Settings, then Devices & Services.
- Use the relay 1 switch (named after your device): turning it on sends one pulse, and the Shelly’s timer returns it to off.
- Wrap it in a script or button. Don’t add it to voice assistants for disarming.
- Because the panel gives no state back, don’t build automations that blindly toggle. Trigger only when you know the current state, for example “arm when everyone leaves” only if you confirm the system was disarmed.
Part J: Final checks
- Walk test: both detectors light the merged zone.
*2: no service faults listed.- If the Service light shows lost system time after the power cut, set the date and time as described in the user manual.
- Close the cabinet and make sure the tamper clears.
- Keep the photos of your final wiring.
7. Add real-time intrusion alerting via AUX 2 (Optional)
By monitoring the panel’s AUX 2 terminal (which activates and drops voltage during an alarm), the Shelly can instantly notify Home Assistant of a real intrusion.
Part A: Wiring the Voltmeter
- Power Down: Unplug the AC plug-pack and disconnect the red battery lead.
- Wire the Shelly: Take the Shelly Plus Uni’s white wire (Analog In). Loosen the screw on the panel’s AUX 2 terminal, insert the white wire alongside any existing wires, and tighten securely.
- Power Up: Reconnect the battery and AC power.
Part B: Shelly Web Configuration
- Open the Shelly’s local web interface by typing its IP address into a browser.
- Go to the Home or Peripherals page, click + Add Component or + Add Peripheral, and select Voltmeter (Analog Input).
- Set the voltage range to 30 V DC and save. The Shelly will now read approximately 13.6 V while the alarm is idle.
Part C: Home Assistant Automation
- In Home Assistant, go to Settings > Devices & Services > Shelly. Click the three dots on your Shelly Plus Uni and select Reload.
- Find the new Voltmeter entity under the device’s Sensors list and copy its exact Entity ID.
- Create a new automation in the Visual Editor. Under Trigger, choose Numeric state, select your Voltmeter entity, and set Below to
3and For to00:00:03. (This 3-second buffer prevents false alarms from micro-voltage drops). - Under Action, choose Call service (or Perform action), select
notify.mobilefor your specific phone, and enter your emergency message (e.g., “? ALARM TRIGGERED ?”). - Optional: Add YAML data to the action (
push: sound: name: default, critical: 1, volume: 1.0) to bypass the phone’s silent switch. Save the automation.
8. Troubleshooting
- Merged zone flashes continuously: the loop is open. Check the wire link where you removed a resistor, the detector covers (tamper), the Wago and any loose screw, and that PIR warm-up has finished.
- Detector’s red LED stays dark: many PIRs disable the LED after warm-up. Check its LED jumper or use the walk test.
- Detector is dead: measure 12 V DC across its power terminals. Re-seat its red and black wires at POS and COM.
- Need two taps in the app: Auto off is not set to 3 seconds.
- Keypad exits when you press
0#: the program code was not accepted. Look for the Service light flashing and the steady function lights after the code, and try 971300. *0beeps: that starts tone adjustment. Press#. The programming entry is*8.- Service light on: press
*2. Common causes are box tamper (cabinet open), lost system time and siren trouble. - Zone 4 flashes after programming: recheck the resistor and relay pair across the zone and its COM.
- Siren chirps or the strobe flashes when arming: normal feedback for keyswitch arming (Feature 22). It chirps once for arm and twice for disarm.
9. Limits and possible upgrades
- Auto-arm and Quick Arm. The panel can arm on a schedule (Features 34 and 36) and arm with the ON key (Feature 16), which needs no hardware.
- Interface modules. An NX584-type interface can give real arm, disarm and zone status to Home Assistant, but compatibility with your firmware is unconfirmed.
10. Key facts
- Zone type 30 = momentary keyswitch, sealed with 3.3 k?.
- Zone light values: 1, 2, 4, 8, 16 for zones 1 to 5; add them to read a number.
- Program entry:
*8, code,0#. Feature 18 = zone types. Feature 22 = system options. - Shelly Plus Uni OUT 1 = potential-free solid-state relay, 30 V and 300 mA.
- Relay settings: Detached, Power on default Off, Auto off 3 seconds.